Electrical Junction Box Sizing Calculator ⚡

Determine the minimum required cubic volume for a box based on NEC 314.16 rules.

Select the largest conductor size in the box.

Number of all current-carrying wires.

Total number of all ground wires. (Counts as 1 volume total)

E.g., NM-B connector built into the box (Counts as 1 volume total)

Number of yoke/strap-mounted devices (Counts as 2 volumes each)

E.g., for ceiling fixtures (Counts as 1 volume each)

Understanding NEC Junction Box Fill Rules

The National Electrical Code (NEC) Section **314.16** specifies the minimum volume required for a box to prevent overcrowding and overheating, which is a significant fire hazard. The calculation is based on **volume allowances** for every component in the box, not just a simple wire count. [Image of Electrical Junction Box with components labeled]

NEC Box Fill Components

Each component is assigned a number of volume allowances, where one allowance equals the cubic inch volume required for the largest conductor size in the box (from NEC Table 314.16(B)).

Component Type Volume Allowance (per component) NEC Reference
Conductors (Hot/Neutral/Traveler/etc.) 1 (For each conductor) 314.16(B)(1)
Equipment Grounding Conductors (EGCs) 1 (Total, regardless of number of EGCs) 314.16(B)(2)
Cable Clamps (Internal to Box) 1 (Total, regardless of number of clamps) 314.16(B)(2)
Support Fittings (Hickeys, Crowfoot) 1 (For each fitting) 314.16(B)(3)
Devices (Switches/Receptacles) 2 (For each single- or multi-gang device) 314.16(B)(4)

Conductor Volume Allowances (Table 314.16(B))

Important NEC Box Fill Notes:

Always select a box with a **marked cubic inch volume** that is equal to or greater than the calculated minimum. Conductors that **pass through** the box without splice or connection are generally exempt, provided they don't exceed twice the conductor size's volume allowance.